Calibration and Start-Up 4-3
DC590+ DRV Series DC Digital Drive
4. Connect power but do not start the drive. The drive should now receive control power and the keypad display should read DC 4Q 35A::MENU
LEVEL (the DC 4Q 35A line may vary depending on your drive).
5. Check that the motor is free to rotate.
Calibrate the Drive
Go to the Configure Drive menu to enter the motor calibration data. This is also a good time to enter other commonly used parameter data.
NOTE To change any parameter in the procedure below, press the M key to access the parameter and then use the arrow keys to change the setting.
When finished, press the E key. At that point you can move to the next parameter.
Keypad Description
Press Display
DC 4Q 35A
MENU LEVEL
The DC 4Q 35A line may vary depending on your drive. This is the top of the menu tree.
MENU LEVEL
DIAGNOSTICS
You are now viewing the level 1 menu headings.
MENU LEVEL
CONFIGURE DRIVE
You have navigated to the CONFIGURE DRIVE menu at level 1.
The CONFIGURE ENABLE parameter contained in this menu allows the calibration settings to be
edited (parameters marked with an asterisk (
*
) in this table). Other parameters in this table can be
changed at any time.
CONFIGURE DRIVE
CONFIGURE ENABLE
This is the CONFIGURE ENABLE parameter. Press
M
again to edit the parameter.
Press
to select ENABLED.
All of the LEDs on the display will flash to indicate the drive is in Configuration mode. The drive will
not run until CONFIGURE ENABLE is set back to DISABLED.
Press
E
to exit.