Installing the Drive 3-15
DC590+ DRV Series DC Digital Drive
Control Wiring
ABC
P3
MOT/THERM
-100
+100
0
10K
POTENTIOMETER
USED AS
SETPOINT RAMP
INPUT
EMERGENCY
STOP RELAY
NORMALLY
OPEN
SWITCH
to control
circuitry
LINK IF
NOT USED
NORMALLY
CONTACT
ON MAIN
OPEN
CONTACTOR
LINK IF
NOT USED
These
terminals
vary in
location
Refer to
Terminal
Locations
diagram
All connections made to terminal blocks A, B and C must be isolated signal voltages. Never perform high voltage resistance or dielectric
strength tests without first completely disconnecting the drive from the circuit being tested.
To comply with EMC requirements, use screened control cables with a minimum cross-section area of 0.75mm
2
(18AWG).
Control wiring should be bundled and routed to the left side of the drive so that the control door on Frames 3, 4, 5 & H is free to open.