Programming  D-85 
DC590+ DRV Series DC Digital Drive   
OP STATION 
MMI Set-up options and Local setpoint information. 
 
 
 
 
 
 
 
OP STATION 
Parameter  Tag  Range 
LOCAL KEY ENABLE  511  FALSE / TRUE 
Enables the LOCAL/REMOTE control key on the op-station. Set to TRUE to allow the operator to toggle between local and remote modes. 
SETPOINT  512  0.00 to 100.00 % 
SET UP menu - Actual value of local setpoint. This value is not persistent. 
JOG SETPOINT  513  0.00 to 100.00 % 
SET UP menu - Actual value of local jog setpoint. This value is not persistent. 
RAMP ACCEL TIME  514  0.1 to 600.0 s 
Acceleration time used while in Local mode. 
RAMP DECEL TIME  515  0.1 to 600.0 s 
Deceleration time used while in Local mode. 
INITIAL DIR  516  REVERSE / FORWARD 
START UP VALUES menu  - Start-up mode of local direction on power-up. Set to TRUE for Forward. 
INITIAL MODE  517  REMOTE / LOCAL 
START UP VALUES menu  - Start-up mode of Keypad LOCAL/REMOTE control key on power-up. Set to TRUE for Local mode. 
INITIAL VIEW  518  LOCAL / PROGRAM 
START UP VALUES menu  - Start-up mode of Keypad PROG key on power-up. Set to TRUE for Program mode to see the local setpoint.