4-26 Calibration and Start-Up
DC590+ DRV Series DC Digital Drive
External Control of the Drive
Remote Sequencing Command
REM. SEQUENCE : Tag 536, Mnemonic "ow", Default = 0x0000 ("0x" denotes a Hexadecimal value)
This is a control word that allows the device to be operated remotely over a field bus. REM. SEQ. ENABLE must be TRUE to enable this function.
NOTE Refer to the RS485 Communications Interface Technical Manual, HA463560U002 on the website, for information about the EI Bisynch
ASCII communications protocol.
Reserved bits are undefined when read and should be set Zero when written.
Bit Number Mask Name Comment
0 (lsb) 0x0001
Remote Enable
1 0x0002
Remote Start
2 0x0004
Remote Jog
3 0x0008
Remote Jog Mode Selects Jog Speed
4 0x0010
Reserved
5 0x0020
Reserved
6 0x0040
Reserved
7 0x0080
Reserved
8 0x0100
Remote Alarm Ack Alarm Acknowledge
9 0x0200
Remote/Remote Trip
Remote Trip (High for OK)
10 0x0400
Reserved
11 0x0800
Reserved
12 0x1000
Reserved
13 0x2000
Reserved
14 (msb) 0x4000
Reserved
15 (msb) 0x8000
Validation This bit must be zero for the command word to be accepted