3-4 Installing the Drive
DC590+ DRV Series DC Digital Drive
Line Reactor/Isolation Transformer
If no isolation transformer is used, we recommend that you always use the specified line reactor with the drive to provide a known supply
impedance for effective operation of the thyristor transient suppression circuits. At least 2% line impedance should be provided in the supply side of
the drive.
Note: On installations requiring compliance with EN61800-3 Table 11, you must fit capacitors between the phase and ground, before the specified
Line Reactor. This applies to DRVs with an armature current <100A.
Refer to Appendix E: “Technical Specifications” - AC Line Reactor for selection details.
590AC Line Choke Filter
CO468398
Contactor
AC
Line
Reactor
Drive
Start
Semi-Conductor
C4
C1, C2 & C3
PE/ground
DRV
Suitable Branch
Protection Fuse
or
Circuit Breaker
Fuses
Figure 3-1 AC Line Reactor and Capacitors fitted to
Frame 1 (35A) & Frame 2 (40A & 70A) DRV
Capacitor Reference Number Capacitor Value/Type
C1, C2, C3
3.0μF 400V, EMI suppressor type Class X1
C4
1.0μF 400V, EMI suppressor type Class X1
Refer to Appendix E: “Technical Specifications” - AC Line Reactor for selection details.