Certification B-7
DC590+ DRV Series DC Digital Drive
Field Grounding Terminals
The field grounding terminal(s) is identified with the International Grounding Symbol (IEC) Publication 417, Symbol 5019.
Field Terminal Kits
UL compliant terminal kits are available for the connection of power wiring for the following Drive ratings. These terminals must be applied with the
correct tooling as described in the Installation Instructions provided with each terminal kit.
NOTE 1580A controller requires two
LA386000U830 kits.
Kit Part Number Controller
Rating (A)
Number of Lugs Purpose Lugs per
Terminal
Wire Size per Lug Cable Rating
LA386000U380
380
3
2
AC
DC
1
1
2 x 4/0 AWG
2 x 250kcmil
230A
255A
LA386000U500
500
3
2
AC
DC
1
1
2 x 300kcmil
2 x 350kcmil
285A
310A
LA386000U725
725
3
4
AC
DC
1
2
2 x 600kcmil
2 x 4/0 AWG
420A
230A
LA386000U830
830
6
4
AC
DC
2
2
2 x 250kcmil
2 x 300kcmil
255A
285A