Programming D-49
DC590+ DRV Series DC Digital Drive
DIGITAL
INPUTS
Use this block to control the
digital operating parameters
of the software.
The digital input can be
configured to point to a
destination location, and to set
that destination TRUE or FALSE
depending upon programmable
values.
DIGITAL INPUTS
Parameter Tag Range
VALUE FOR TRUE 103, 106, 109, 1239 -300.00 to 300.00 %
The output value when input is TRUE, that is:
Digital Input 1, terminal C6 = 24V (True)
Digital Input 2, terminal C7 = 24V (True)
Digital Input 3, terminal C8 = 24V (True)
VALUE FOR FALSE 104, 107, 110, 1240 -300.00 to 300.00 %
The output value when input is FALSE, that is:
Digital Input 1, terminal C6 = 0V (False)
Digital Input 2, terminal C7 = 0V (False)
Digital Input 3, terminal C8 = 0V (False)
OUTPUT 680, 681, 682, 1238
.xx %
The output value, this is either VALUE FOR TRUE or VALUE FOR FALSE.
DIGIN 1 (C6) to DIGITAL INPUT C5 71, 72, 73, 69 OFF / ON
The Boolean representation of the actual voltage applied to the terminal.