598P/599P Application Manual
Technical Specification
ENVIRONMENTAL DATA
Operating Temperature
0 to +45°C
Storage Temperature -25 to +55°C
Shipping Temperature -25 to +70°C
Enclosure Rating IP20
Altitude Rating Maximum Altitude 500 metres.
De-rate the Output at 1% per 200 metres.
Humidity Maximum 85% relative Humidity at 45°C non-condensing.
Atmosphere Non flammable, non-corrosive and dust free.
Climatic Class 3k3 as defined by EN60721-3-3 (1995).
Safety Designed to : -
Europe EN50178 when enclosure mounted.
Overvoltage Category III
Pollution Degree 2
ELECTRICAL RATINGS
Coding Supply Voltage
110 240 Vac ±10% 3ph Low Voltage Build
220 500 Vac ±10% 3ph Medium Voltage Build
380 690 Vac ±10% 3ph High Voltage Build
Field Supply Voltage 110 240 Vac ±10% 1ph Low Voltage Build
*220 500 Vac ±10% 1ph Medium Voltage Build
*380 690 Vac ±10% 1ph High Voltage Build
*
The field supply of the 220-500V and 380-690Vac rated products must
be derived from line-to-line of a 3 phase supply, NOT from line-to-neutral.
Supply Frequency
50/60 Hz ±10%
Armature Thyristor
Firing Isolation
Suitable for external stack supply system rated:
Overvoltage Category III
Max. 500Vac rms for Medium Voltage Build
Max. 690Vac rms for High Voltage Build
Output Current
60 Amps dc naturally cooled - 120 amps dc Force Cooled.
De-rate linearly at 1% per °C above rated temperature.
Supply Current
Field Coding
(1 times Field Current dc value) Amps 1ph ac.
Nominal 3ph ac.
Field Output Voltage
(0.9 times 1ph Supply Voltage) V dc
Total Losses (3 times Idc out) Watts.
Auxiliary Supply 110 240 Vac ±10% 1ph Naturally Cooled.
110 120 Vac ±10% 1ph Force Cooled 115 Vac Fan configuration.
220 240 Vac ±10% 1ph Force Cooled 230 Vac Fan configuration.
Auxiliary Supply Current SMPS Quiescent Current 500mA 115 Vac or 250mA 230 Vac i.e. 50 VA.
Fan Current - 270mA @ 115 Vac or 135mA @ 230 Vac.
Auxiliary Supply Fuse 3 Amps.
FIELD FUSING
DC Output Supply Voltage Semiconductor I
2
t Fuse Rating Fuse I
2
t Parker SSD Part
No.
60 Amps 500 Vac 19100 A
2
s 80 amps 2550 A
2
s CH570084
120 Amps 500 Vac 19100 A
2
s 125 amps 8500 A
2
s CH571253
60 Amps
690 Vac
8830 A
2
s
80 amps
2550 A
2
s
CH570084
120 Amps 690 Vac 8830 A
2
s 125 amps 8500 A
2
s CH571253