EasyManua.ls Logo

Parker 890CS - 4.1: Power-up with 24 V DC

Parker 890CS
586 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
890SD Standalone Drive
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page 5-29
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
4.1: Power-up with 24V DC
You must provide an external 0V and +24V DC (±10%)
control supply. Each unit can draw 2A, so for example: 3
units = 6A.
Connect 24V DC to terminal X13/01 or X13/02, and 0V
(24V) to terminal X13/03 or X13/04. The units are protected
against reversal of this 24V DC supply.
Use the spare X13 terminals to daisy-chain the control supply
to other drives in the system.
The diagram shows the control supply daisy-chained between
890SD Standalone Drives.
IMPORTANT This Control Supply will power the unit for configuration
purposes. It is not required when the 3-phase supply is
present, but can be left connected.
24V DC
890SD
Drives
External
24V DC
Supply

Table of Contents

Other manuals for Parker 890CS

Related product manuals