Programming  
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D  Page D-79 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
PHASE INCH 
SETUP::PHASE CONTROL::PHASE INCH 
CLOSED-LOOP VEC Motor Control Mode only. 
Used with the external registration controller to advance/retard the Load reference position with respect to the Master position. 
Parameter Descriptions 
ADVANCE 
PREF: 108.01  Default: FALSE  Range: FALSE / TRUE 
Command to Inch the load forwards. While TRUE, counts are added to the error calculator at a rate given by RATE. Note: if 
both ADVANCE and RETARD are TRUE then no action is taken. 
RETARD 
PREF: 108.02  Default: FALSE  Range: FALSE / TRUE 
Command to Inch the load backwards. While TRUE, counts are subtracted from the error calculator at a rate given by RATE. 
RESET 
PREF: 108.09  Default: FALSE  Range: FALSE / TRUE 
This parameter, when TRUE, resets the Inch Offset to zero. The block may only be reset while the position loop is not 
operating. 
RATE 
PREF: 108.03  Default: 0.1000  Range: 0.0001 to 30.0000 
Speed of the Inch in load rev/s and the rate at which counts are added to the error calculator. A rate of 0.05 with a system 
scaled in revolutions would cause the drive to advance at a rate of 0.05 revolutions a second with respect to the master. 
RATE SCALE 
PREF: 108.08  Default: 1.000  Range: 0.001 to 30.000 
Gain applied to Rate to allow fine control of Inch Rate. This allows fine control over the inch rate by scaling the value of 
RATE. Actual Rate = RATE x RATE SCALE 
OFFSET 
PREF: 108.10  Default: —.xxxx  Range: —.xxxx 
This diagnostic shows the position offset generated by the block (1.0 = 1 load mechanical revolution). This output is persistent. 
ACTIVE 
PREF: 108.04  Default: FALSE  Range: FALSE / TRUE 
This diagnostic display True while Advance or Retard actions are active.