Trips and Fault Finding
Page 10-14 890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
DISABLE TRIPS, DISABLE TRIPS+
The DISABLE TRIPS, ACTIVE TRIPS, WARNINGS, TRIGGERS 1 and TRIGGERS 2 parameters use a
four digit hexadecimal number to identify individual trips. Each trip has a unique corresponding number as
shown below.
Trip Name (MMI) Value Mask User Disable Auto-restart
NO TRIP 0 0x0000 N/A N/A
OVERVOLTAGE 1 0x0001 No Yes
UNDERVOLTAGE 2 0x0002 No Yes
OVERCURRENT 3 0x0004 No Yes
HEATSINK 4 0x0008 No Yes
EXTERNAL TRIP 5 0x0010 No Yes
INPUT 1 BREAK 6 0x0020 Yes Yes
INPUT 2 BREAK 7 0x0040 Yes Yes
MOTOR STALLED 8 0x0080 Yes Yes
INVERSE TIME 9 0x0100 Yes Yes
BRAKE RESISTOR 10 0x0200 Yes Yes
BRAKE SWITCH 11 0x0400 Yes Yes
OP STATION 12 0x0800 Yes Yes
LOST COMMS 13 0x1000 Yes Yes
CONTACTOR FBK 14 0x2000 Yes Yes
SPEED FEEDBACK 15 0x4000 Yes Yes
AMBIENT TEMP 16 0x8000 No Yes
MOTOR OVERTEMP 17 0x0001 Yes Yes
CURRENT LIMIT 18 0x0002 No Yes
24V FAILURE 20 0x0008 Yes Yes
LOW SPEED OVER I 21 0x0010 No Yes
PHASE FAIL 22 0x0020 Yes Yes

Table of Contents