Electrical Ratings: 890CD Frame D, 380-500V
Input currents listed at 560V DC and 650V DC assuming total source impedance of 190μH. Motor power, input current and
output current must not be exceeded under steady state operating conditions.
Model Number
890CD/5/0039D 890CD/5/0045D 890/5/0059D
Nominal Supply Voltage
560Vdc 650-705Vdc 560Vdc 650-705Vdc 560Vdc 650-705Vdc
Motor Power 18.5kW 25Hp 22kW 30Hp 30kW 40Hp
Vector Mode
Input Current A 44 41 51 46 66 59
Output Current @ 3kHz A 39 35 45 40 59 52
Power Loss @ 3kHz W 256 235 260 240 393 354
Output Current @ 6kHz A 32 29 36 34 42 36
Power Loss @ 6kHz W 290 270 273 275 384 382
Output Overload Motoring 150% overload for 60 seconds
Servo Mode
Input Current A 44 41 51 46 66 59
Output Current @ 4kHz A 35 29 38 34 50 45
Power Loss @ 4kHz W 252 226 278 250 362 337
Output Current @ 8kHz A 26 20 28 25 31 27
Power Loss @ 8kHz W 293 278 319 311 368 357
Output Overload Motoring 200% overload for 4 seconds