Power Connections - 890SD Standalone Drive
Power Connections - 890SD Standalone Drive
EARTH/GROUND
Fix Drive earth connections to .
Maximum wire sizes:
Frame B: 6mm
2
/ 10AWG
Frame C: 10mm
2
/ 8AWG
Frame D: 16mm
2
/ 4AWG
Fix the earth from the Motor to the base of the drive.
Maximum wire sizes:
Frame B: 4mm
2
/ 12AWG
Frame C: 10mm
2
/ 8AWG
Frame D: 16mm
2
/ 4AWG
Refer to the 890 Installation Kit for earth/ground fixing details.
Each unit must be permanently earthed according to EN 50178.
For permanent earthing: one conductor, PE1, of >10mm² cross-section is required; or two individual
incoming protective earth conductors, PE1 & PE2, of <10mm² cross-section. Each earth conductor must
be suitable for the fault current according to EN 60204.