890CS & 890CD Common Bus Units   
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D  Page 4-25 
8 
9 
10 
11 
 
B 
C 
D 
1 
2 
3 
4 
5 
6 
7 
E 
8 
9 
1 
2 
3 
4 
5 
6 
E 
Control Connections - 890CS Common Bus Supply  
The table below shows the factory defaults.  
 
Name Range  Description 
01 
02 
+24V AUX 
SUPPLY 
24V (±10%) 2A 
03 
X01
04 
0V AUX 
SUPPLY 
0V (24V) 
You must supply 24V DC to power the unit. 
Use a source separate to your 3∅ supply. 
Use the second set of terminals to daisy-
chain to the next drive. Connect three 
890CD units only using this method. The 
unit is protected against reversal of this 
supply. See Note. 
01  +24V OUT  24V  A 24V DC supply for the digital I/O of X02. 
02  DIGIN1  -  Future use 
03  ENABLE  0-24V 
24V = 890CS Common Bus Supply powers-
up to supply DC to connected units. 
05  AOUT MODE  0-24V 
0V = Power (kW) , 24V = Current (A). 
Selects the units for meter connected to 
AOUT. 
05  AOUT  0-10V 
Mode set by AOUT MODE. Meter 
connection: 
0 to 5V is equivalent to 0 to 100%. 
X02
06  0V OUT  0V  0V reference for AOUT 
Note  X01: This Control Supply is necessary at all times to operate the 890CS Common Bus 
Supply. DO NOT use this 24V for the terminals at X02, only use the 24V supply 
provided at X02/01. 
230V
400/460V
500V
30
SUPPLY
ENABLE
OUT MODE
AOUT
0V OUT
HMI - REMOTE
WARNING
HEALTH
PRE-TRIP
S1