EasyManua.ls Logo

Parker 890CS - DYNAMIC BRAKING

Parker 890CS
586 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page D-27
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
DYNAMIC BRAKING
SETUP::MOTOR CONTROL::DYNAMIC BRAKING
Designed for all Motor Control Modes.
The dynamic braking function block controls the rate at which energy from a regenerating motor is dumped into a resistive
load. This dumping prevents the dc link voltage reaching levels which would cause an Overvoltage trip.
Parameter Descriptions
ENABLE
PREF: 99.01 Default: TRUE Range: FALSE / TRUE
Enables operation of the dynamic braking block.
BRAKE RESISTANCE
PREF: 99.03 Default: 100.00 Ohm Range:0.01 to 300.00 Ohm
The value of the dynamic braking load resistance.
BRAKE POWER
PREF: 99.04 Default: 0.1 kW Range: 0.1 to 510.0 kW
The power that the load resistance may continually dissipate.
1SEC OVER RATING
PREF: 99.05 Default: 25 Range: 1 to 40
Multiplier that may be applied to BRAKE POWER for power overloads lasting no more than 1 second.
INT DB RESISTOR
PREF: 99.07 Default: TRUE Range: FALSE / TRUE
For futrue use only. Set to FALSE if an external dynamic brake resistor is fitted.
BRAKING
PREF: 99.06 Default: FALSE Range: FALSE / TRUE
A read-only parameter indicating the state of the brake switch.