Programming
Page D-116 890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
Parameter Descriptions
SEQUENCER STATE
PREF: 92.22 Default:0 Range: See below
This parameter indicates the current sequencing state:
Enumerated Value : State
0 : START DISABLED
1 : START ENABLED
2 : SWITCHED ON
3 : READY
4 : ENABLED
5 : F-STOP ACTIVE
6 : TRIP ACTIVE
7 : TRIPPED
Refer to Appendix B : “Sequencing Logic States”.
REMOTE REV OUT
PREF: 92.23 Default: FALSE Range: FALSE / TRUE
This parameter indicates the current state of remote direction and RUN REVERSE. Note - this is the demanded direction, not
the actual direction.
HEALTHY
PREF: 92.24 Default: TRUE Range: FALSE / TRUE
Set FALSE when the Drive trips, and set TRUE when the run command is removed.
FAN RUNNING
PREF: 92.26 Default: FALSE Range: FALSE / TRUE
This can be used to control the running of externally supplied fans. True when the drive is running, goes FALSE 60 seconds
after the drive has stopped. Can be used to control externally supplied fans in large 890 drives.