19/20
ICEP080E-ICEP120E
6 Opsporen van storingen
STORING
OORZAAK
OPLOSSING
DE TEMPERATUUR VAN HET
AFVOERWATER IS HOGER DAN DE
INGESTELDEWAARDE
DE COMPRESSOR WORDT UITGE-
SCHAKELD DOOR INGRIJPEN VAN DE
HOGEDRUKSCHAKELAAR
AANZUIGING
COMPRESSOR,
VLOEISTOFLIJN
MET IJZELVORMING
DE COMPRESSOR
WERKT LANG,
MAAKT LAWAAI
WATERTOEVOER
OVERMATIG,
HOGEWARMTEBELASTING
TOEVOER VAN
TE KOELEN
VLOEISTOF
VERMINDEREN
OMGEVINGS
TEMPERATUUR
HOOG
DE OMGEVINGSTEMPE-
RATUUR
TERUGBRENGEN
ONDER GRENSWAARDE
DRUKSCHAKELAAR
DEFECT OF
ONTREGELD
VERVANG DE
DRUKSCHAKELAAR
KOELERFILTER
VERSTOPT
FILTER
VERVANGEN
VINNEN VAN
CONDENSATOR
VUIL
VINNEN VAN
CONDENSATOR
REINIGEN
OPPERVLAK VAN
CONDENSATOR
VERSTOPT
VOORKANT VAN
DE CONDENSATOR
VRIJMAKEN
WATERTOEVOER
ONVOLDOENDE
TOEVOER VAN TE
KOELEN VLOEISTOF
VERHOGEN
COMPONENTEN
COMPRESSOR
AANGETAST
HERSTELLEN
OF COMPRESSOR
VERVANGEN
LEKKAGE IN
CIRCUIT,
AFVOERINSTALLATIE
OP LEKKAGE
CONTROLEREN,
VERHELPEN, CIRCUIT
VULLEN
KOELERFILTER
VERSTOPT
FILTER
VERVANGEN
JA
NEE
JA
JA JA
JA JA
JA
JA
JA
JA
NEE
NEE
NEE
NEE
DE COMPRESSORWORDT UITGE-
SCHAKELD DOOR INGRIJPEN VAN DE
LAGEDRUKSCHAKELAAR
NEE
VENTILATOR DRAAIT IN
VERKEERDE RICHTING
NEE
FASEN
OMKEREN
BALLON THERMO-
STAATKLEP LEEG
NEE
THERMOSTAAT
KLEP
ONTREGELD
NEE
KLEP
VERVANGEN
KLEP OPNIEUW
AFSTELLEN
JA
JA
NEE
NEE