6 Troubleshooting
FAULT
CAUSE
REMEDY
THE OUTLET WATER
TEMPERATURE EXCEEDS THE SET
VALUE
COMPRESSOR STOPS DUE
TO OPERATION OF THE HIGH
PRESSURE
SWITCH
COMPRESSOR SUCTION, LIQUID
LINE FROSTED
THE COMPRESSOR RUNS FOR
LONG PERIODS, IS NOISY
EXCESSIVE
WATER FLOW,
HIGH THERMAL
LOAD
REDUCE THE FLOW RATE OF THE-
WATER TO BE COOLED
HIGH
AMBIENT
TEMPERATURE
RETURN THE
AMBIENT
TEMPERATURE TO
BELOW THE
SPECIFIED LIMIT
PRESSURE SWITCH BROKEN OR
INCORRECTLY CALIBRATED
REPLACE
PRESSURE SWITCH
REFRIGE---
RANT FILTER
CLOGGED
RENEW
THE FILTER
CONDENSER
FINS
DIRTY
CLEAN THE
FINS OF THE
CONDENSER
CONDENSER
SURFACES
CLOGGED
CLEAR THE FRONT SURFACE
OF THE CONDENSER
INSUFFICIENT
WATER FLOW
INCREASE THE FLOW
RATE OF THE FLUID TO
BE COOLED
COMPRESSOR
COMPONENTS
DETERIORATED
REPAIR OR
REPLACE
COMPRESSOR
LEAKS IN CIRCUIT,
SYSTEM DISCHARGED
CHECK FOR
LEAKS, REPAIR,
CHARGE THE
CIRCUIT
REFRIGERANT FILTER
CLOGGED
RENEW
THE FILTER
yes
no
yes
yes yes
yes
yes
yes
yes
yes
yes
no
no
no
no
COMPRESSOR STOPS DUE
TO OPERATION OF THE
LOW PRESSURE SWITCH
no
FAN ROTATES
BACKWARDS
no
SWAP OVER THE
PHASEWIRES
THERMOSTATIC
BULB
DISCHARGED
no
EXPANSION
VALVE
INCORRECTLY
CALIBRATED
no
RENEW
THE VALVE
RECALIBRATE
THE VALVE
yes
yes
no
no