PAGE 29
STEP DESCRIPION DISPLAY AVAILABLE FACTORY YOUR
CODE SETTINGS SETTING SETTING
5 Output 2 out2 0 = None Position
0
Proportioning Direct (Close)
1 = On-Off Direct (Cooling)
2 = On-Off Reverse (Heating)
3 = Time Proportioning-
Direct (Cooling)
4 = Time Proportioning-Reverse
(Heating)
5 = Current Proportioning-
Direct (Cooling)
6 = Current Proportioning-
Reverse (Heating)
7 = Position Proportioning
Reverse (Close)
6 Output 2 o2PL 0 to 100%
100
Percent Limit
7 Output 3 out3 0 = None
0
1 = Process Alarm-Direct
2 = Process Alarm-Reverse
3 = Deviation Alarm-Direct
4 = Deviation Alarm-Reverse
5 = Deviation Band Alarm-
Open within band
6 = Deviation Band Alarm-
Closed within band
8 Relay A rLyA 0 = Not assigned
1
Assignment 1 = Assigned to Output 1
2 = Assigned to Output 2
3 = Assigned to Output 3
4 = % Output Relay Actuation
(EA Option)
9 Relay B rLyb Same selection as Relay A
2
Assignment
10 Relay C rLyC Same selection as Relay A
3
Assignment
11 Display Select diSP 1 = Process Value (PV)
1
2 = PV and Setpoint
3 = Deviation
4 = Deviation and Setpoint
5 = Setpoint
12 Decimal Position dPoS 0 or 1 for T/C and RTD Input
0
0 to 3 for volt/mV Input
13 Engineering units Euu -9999 to 9999
1000
Upper Value
14 Engineering units EuL -9999 to 9999
0
Lower Value
15 Hysteresis for HySt 0 to 300°/Units
3
On/Off Outputs (width of hysteresis band)
16 Remote Setpoint rSP 0 = None
0
1 = 1 to 5 Volts DC
2 = 0 to 5 Volts DC
3 = Contact Closure Sensing
for SP=PV (EA Option)