PAGE 30
17 Remote Setpoint rSPu -9999 to 9999°/Units
1400*
Upper Value
18 Remote Setpoint rSPL -9999 to 9999°/Units
0
Lower Value
19 Setpoint SPL -9999 to 9999°/Units
1400*
Upper Limit (SPuL - EA Option)
20 Setpoint SPLL (EA Option) ± 9999 0
Lower Limit
21 Automatic Transfer AtFr 0 = No automatic transfer
0
1 = Transfer when PV
goes below setpoint
2 = Transfer when PV
goes above setpoint
22 Process PFF 1 to 20 (# of scans averaged)
1
Filter Factor 1 = no filtering
23 Display dFF 1 to 20 (# of scans averaged)
1
Filter Factor 1 = No Filtering
* Whenever inPS is changed, the parameter is set to the upper limit of advertised span.
Extended Features Software Options (EA)
24 Fast Scan FSCn 0 = Standard Scan -
0
1 scans/second
1= Fast Scan -
3 scans/second
25 Process Rounding Prnd 1 to 100 degrees/units
1
1, 0.1, 0.01, 0.001 = no
rounding depending on dPoS
26 Current Output 1 Co1r 0 = 0 to 20mADC
1
1 = 4 to 20mADC
27 Current Output 2 Co2r 0 = 0 to 20mADC
1
1 = 4 to 20mADC
28 Process Output Pout 0 = Not selected
0
1 = Process Assigned to
Current Output 1
2 = Process Assigned to
Current Output 2
3 = Setpoint Assigned to
Current Output 1
4 = Setpoint Assigned to
Current Output 2
29 Process/Setpoint Pou -9999 to 9999 degrees/units
2000
Output Upper Value
30 Process/Setpoint PoL -9999 to 9999 degrees/units
0
Output Lower Value
STEP DESCRIPTION DISPLAY AVAILABLE FACTORY YOUR
CODE SETTINGS SETTING SETTING