5.7. Regeneration types
Volumetric
The controller monitors the volume of water used. Once it calculates that system capacity is reached,
a regeneration cycle will be initiated immediately or at a pre-set time.
Immediate control: The controller measures water usage and regenerates the system as soon
as the system capacity is reached;
delayed control: The controller measures water usage and regenerates the system, at the
specified regeneration time (02h00), after the system capacity is reached.
Time clock control
This control regenerates the system on a weekly schedule. The schedule is defined on the skipper
wheel The control will initiate a regeneration cycle on days that have been set to “ON”.
The system can be set to regenerate on one to every days of the week or on a 2, 3, 4, 6 or 12 days
period.