EasyManua.ls Logo

Phoenix Contact EV Charge Control Basic - Modbus Description; Modbus Register Types

Phoenix Contact EV Charge Control Basic
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus description
106377_en_04 PHOENIX CONTACT 53 / 68
9 Modbus description
You can access the device registers via Modbus/RTU. Modbus/RTU can be used to addi-
tionally configure the device, request status information, and access and control the
charging process. The device operates as a Modbus slave. The slave address is set via
S2/DIP 2 6. The baud rate (9600 or 19200) for communication is set via S2/DIP 1. See
Table “Configuration switches S1 + S2” on page 13.
9.1 Modbus register types
Modbus/RTU supports three register types which are used as follows.
Table 9-1 Modbus registers
Modbus register type Value Access
Input 16 bits Read
Holding 16 bits Read/write
Coils 1 bit Read/write

Table of Contents

Related product manuals