EasyManua.ls Logo

Pilz PSS 3075-3 Series - Example: Dual-Channel, Failsafe Input Devices, Without Test Pulses

Pilz PSS 3075-3 Series
98 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring the Inputs and Outputs
7-8 Operating Manual: PSS 3075-3 Series
Example: Dual-channel, failsafe input devices, without test pulses
Features:
• Depending on the application area and its respective regulations, this
connection diagram is suitable for input devices with frequent operation
and diverse channels, up to category 4 in accordance with EN 954-1,
provided the functionality of both input device channels is monitored in
the user program via a feasibility check.
• Depending on the application area and its respective regulations, this
connection diagram is suitable for input devices with infrequent
operation up to category 3 in accordance with EN 954-1, provided the
functionality of both input device channels is monitored in the user pro-
gram via a feasibility check.
The possibility of a short circuit occurring between adjacent terminals
cannot be eliminated. For this reason, the two identical (homogenous)
channels on an input device must not be connected to adjacent inputs.
If you are using input devices with different (diverse) channels, adjacent
inputs may be used. Short circuits will be detected in the user program
via the feasibility check.
CAUTION!
A short circuit in the cable between the input device and input with the L+
line or between adjacent inputs will not be detected. Depending on the
type of input device connected, this could create a risk to both personnel
and machinery (e.g. E-STOP). Always ensure that the unit is suitably wired
to eliminate the risk of short circuits.

Table of Contents