29
See
remark 1
this
parameter,
and
will
assume one
of the listed
values
Water
Set TC2 as 2s
and P.B.M as
2.50.
34
See
remark 1
Proportional
band
multiplier for
cooling
action
1.00 … 5.00 Proportional
band for cooling
is given by the
value of
(parameter 15)
multiplied for the
value of this
parameter
(default 1.00)
35
ATR121
ATR141
See
remark 1
In Heating/
Cooling PID
this
parameter
defines the
combinations
of dead band
for heating
and cooling
action
-20…50 %
of value
Negative value
means dead
band, positive
value means
overlapping
(default 0)
36
See
remark 1
Cycle time
for cooling
output
1…300 Seconds
(default 10)