31 
15 - MANUAL START OF TUNING 
Select parameter   as   (manual start) 
 
  Press  Display  Do 
 
1 
 
Display shows   
 
 
2 
 
Display shows   
 
 
3 
 
or 
wait for 4 
seconds. 
Display will show  
process value and 
 alternately until 
the function is 
completed (it may take 
a few minutes). 
To interrupt the 
function press   and 
press    to select 
. 
 
16 - AUTOTUNING 
Parameter   must be selected as  . Autotuning 
starts automatically when the controller is switched-on or when 
setpoint value has been modified. Display alternates between 
process value and the writing   until the function has 
been completed (it may take a few minutes).  
To interrupt the function, press   and press   to select 
. 
 
 
 
 
 
 
 
 
 
32 
17 - FUNCTION LATCH ON 
For  application  with  linear  potentiometers 
 
(potentiometer  ≤  6K)  and 
  (potentiometer  ≤  150K)  or 
0…10Volt  ,  0/4…20mA  inputs,  the  lower  limit  of  scale  (see 
parameter
) can be set to minimum position of sensor; 
it  is  also  possible  to  set  the  upper  limit  of  scale  (parameter 
) to the max. position of sensor and this can be done 
directly on site. 
The  option  “virtual  zero”  (selecting 
  or  )  allows 
also to fix the point where the controller will read zero (but still 
keeping the range of scale between 
 and    .  
Selecting 
  virtual  zero  must  be  reprogrammed  at  each 
starting  of  the  controller;  selecting 
  virtual  zero  will  be 
stored after first calibration.  
To enable function LATCH ON, select chosen configuration for 
parameter 
2
  .  For  calibration  function  follow  the  table 
below.  
 
  Press  Display  Do 
 
1 
 
 
Leave configuration 
mode. 
Display shows cycling 
process value and writing  
. 
Set the sensor on 
minimum operating 
value (corresponding to 
) 
 
2 
 
 
Store minimum value. 
Display shows 
 
Set the sensor on max. 
operating value 
(corresponding 
to
 ) 
    
2
 Calibration function exits configuration mode after that the 
relevant parameter has been modified.