19 - SERIAL COMMUNICATION 
Serial  communication  RS485  and  protocol  MODBUS  –  RTU 
enable  the  controller  ATR121/141  to  receive  and  exchange 
data,  allowing  the  connection  of  more  units  to  a  centralized 
supervisory  system.  The  device  can  be  configured  only  as 
Slave unit. 
LT (line termination) resistors on RS485 line must be removed 
to avoid anomalies. 
Each controller will respond to a request only if it contains the 
same address which is written on parameter 
. The range 
of  admitted  addresses  is  1  –  254.  Address  255  is  used  to 
communicate with all the connected units (Broadcast modality). 
Single  units  ATR121/141  on  the  same  line  cannot  have  the 
same address. Selecting 0 all connected units receive request 
but no answer is required. ATR121/141 may delay the answer 
to  request.  This  delay  (expressed  as  milliseconds)  must  be 
entered on parameter 
 
After  each  parameters  change,  the  controller  stores  the  new 
values  on  EEPROM  memory  (  100000  writing).  Modified 
sepoint  values  are  stored  on  EEPROM  memory  with  10 
seconds delay.  
**  Any  operation  on  words  which  are  not  listed  in  the  table 
below may cause anomalies or malfunction. 
Baud-rate 
Selectable by parameter 
 
MD.1 = 300bit/s 
MD.2 = 9600bit/s 
MD.3 = 19200bit/s 
MD.4 = 38400bit/s 
Format  8, N, 1 (8bit, no parity, 1 stop) 
Supported 
functions 
WORD READING (max 20 word)      (0x03, 0x04) 
SINGLE WORD WRITING                (0x06) 
MULTIPLE WORDS WRITING         (0x10)