30 - ATR142 - User manual
1013
Error flags
Bit0 = Eeprom writing error
Bit1 = Eeprom reading error
Bit2 = Cold junction error
Bit3 = Process error (sensor)
Bit4 = Generic error
Bit5 = Hardware error
Bit6 = Master off-line
Bit7 = Missing calibration data
RO 0
1014
Cold junction temperature
(tenths of degree)
RO -
1015
Start/Stop
0=controller in STOP
1=controller in START
R/W 0
1016
Lock conversion ON/OFF
0=Lock conversion off
1=Lock conversion on
R/W 0
1017
Tuning ON/OFF
0=Tuning off
1=Tuning on
R/W 0
1018
Automatic/manual selection
0=automatic
1=manual
R/W 0
1019 OFF LINE* time (milliseconds) R/W 0
1100
Process visualized (decimal as
display)
RO -
1101
Visualized Setpoint 1 (decimal as
display)
R/W EEPROM
1102
Visualized Setpoint 2 (decimal as
display)
R/W EEPROM
1103
Visualized Setpoint 3 (decimal as
display)
R/W EEPROM
1104
Visualized Setpoint 4 (decimal as
display)
R/W EEPROM
1105
Visualized Alarm 1 (decimal as
display)
R/W EEPROM