ATR401 - User manual 27
Modbus
address
Descrizione Read Write
Reset
value
5 Slave address R/W EEPROM
6 Boot version RO EEPROM
50 Automatic addressing WO -
51 Installation code comparison WO -
500
Loading Default values:
9999 Restore all values
9998 Restore all values except for baud-rate
and slave address
9997 Restore all values except for baud-rate
9996 Restore all values except for slave
address
R/W 0
900
Process AI1 (degrees with tenths of degree for
temperature sensors; digits for linear sensors)
RO -
901
Process AI2 (degrees with tenths of degree for
temperature sensors; digits for linear sensors)
RO -
902
Average AI1-AI2 (degrees with tenths of
degree for temperature sensors; digits for
linear sensors)
RO -
903
Di erence AI1-AI2 (degrees with tenths of
degree for temperature sensors; digits for
linear sensors)
RO -
904
Di erence AI1-AI2 as absolute value (degrees
with tenths of degree for temperature sensors;
digits for linear sensors)
RO -
905
Addition AI1-AI2 (degrees with tenths of
degree for temperature sensors; digits for
linear sensors)
RO -
1000
Command process (degrees with tenths of
degree for temperature sensors; digits for
linear sensors)
RO -
1001 Setpoint 1 R/W EEPROM
1002 Setpoint 2 R/W EEPROM
1003 Setpoint 3 R/W EEPROM
1004 Setpoint 4 R/W EEPROM
1005 Alarm 1 R/W EEPROM