EasyManua.ls Logo

Pixsys ATR 401 - Heating-Cooling P.I.D

Pixsys ATR 401
124 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ATR401 - User manual 23
Press Display Do
4
SET
Set virtual zero. Display shows
 NB: If “Virtual zero at
start”is selected, point 4 must
be repeated at each starting.
To exit procedure press
FNC
.
9.1 Heating-Cooling P.I.D.
ATR401 is suitable also for applications requiring a combined heating-cooling
P.I.D. action.
Command output must be con gured as Heating P.I.D.
(  =  and  greater than 0 and one of alarms
(, ,  or ) has to be con gured as 
Command output must be connected to actuator responsible for heating
action, while alarm will control the cooling action.
Parameters to con gure for Heating P.I.D. are:
 =  Command output action type (Heating);
 : Proportional band Heating;
 : Integral time Heating and cooling;
 : Derivative time Heating and cooling;
 : Cycle time Heating.
Con guration parameters for Cooling P.I.D. are (example: action associated
to alarm 1):
 =  Alarm 1 selection (Cooling);
 : Proportional band multiplier;
: Overlapping / Dead band;
: Cycle time Cooling.
Parameter  (that ranges from 1.00 to 5.00) sets the proportional band
for cooling action, according to the formula here below:
Proportional band cooling action =  x 
In this way it is possible to have a proportional band for cooling action that
will be equal to heating proportional band if  = 1.00, or 5 times greater
if  = 5.00.

Table of Contents

Related product manuals