46 - DRR245 - User manual
67
re t r.
Retransmission
Retransmission for output 0-10 V or 4..20 mA (Short-circuit pins 9 and 10
to use linear output in Volt). Parameters 68 and 69 define the lower and
upper limits of the scale.
di s .
Disabled
u o . p.
Retransmits process in Volt
m a . p.
Retransmits process in mA
u o . c.
Retransmits command setpoint in Volt
m a . c.
Retransmits command setpoint in mA
uo.o.p.
Volt output percentage
ma.o.p.
mA output percentage
uo.a.1
Volt alarm 1 setpoint
ma.a.1
mA alarm 1 setpoint
uo.a.2
Volt alarm 2 setpoint
ma.a.2
mA alarm 2 setpoint
uo.t.a.
Volt T.A.
ma.t.a.
mA T.A.
68
Lo . L. r.
Lower Limit Retransmission
Output V / mA retransmission lower limit range
-999..+9999 [digit
1 p. 55
] (degrees.tenths for temperature sensors), Default:
0.
69
up.L.r.
Upper Limit Retransmission
Output V / mA retransmission upper limit range
-999..+9999 [
digit
1 p. 55
] (degrees.tenths for temperature sensors), Default:
1000.
70
bd . rt.
Baud Rate
Select baud rate for serial communication
4.8 k
4.800 Bit/s
9.6 k
9.600 Bit/s
19.2k
19.200 Bit/s (Default)
28.8k
28.800 Bit/s
39 .4 k
39.400 Bit/s
57.6k
57.600 Bit/s