2 Important technical data
2.1 Analog inputs r sections 3 and 6.9
INP 1: universal input, configurable for thermocouples, resistance thermometers, tem
perature difference, resistance transducers, DC current and DC voltage
INP 3 and INP 4 (option C): DC current, INP 5: DC current and DC voltage
INP 6: resistance transducer and DC current
2.2 Digital inputs
Opto-coupler for 24 V DC, current sink to IEC 1131 type 1, logic 0 = -3...5 V, logic 1 = 15...30 V, approx. 5 mA
di1 and di2: in all versions,
di3...di7: in option B,
di4...di12: in option C.
2.3 Outputs r section 6.10
Relay contact rating: 500 VA, 250 V,2Aat48...62 Hz
OUT1, OUT2, relay or current or logic dependent of version,
OUT4, OUT5:
OUT 3 (option C): current
2.4 Control outputs
Opto-coupler, grounded load with common positive control voltage, power 18...32 V DC ß 100 mA.
do1...do4: in option B,
do5 and do6: in option C
2.5 Supply voltage
90...260V AC, 48...62 Hz, power consumption approx. 10 VA (equipped with all possible options)
For detailed technical data, see data sheet 9498 737 32133.
2.6 Further "modular" in- and outputs
Further analog and digital inputs and outputs can be provided on the "modular C card"
r see KS98 I/O-extension modules on page 225 ff
2.7 Further external in- and outputs
Further analog and digital inputs and outputs can be connected via CANopen.
r see KS98+ I/O extensions with CANopen page 117 ff