EasyManuals Logo

PMA KS 98 User Manual

PMA KS 98
246 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
2 Important technical data
2.1 Analog inputs r sections 3 and 6.9
INP 1: universal input, configurable for thermocouples, resistance thermometers, tem
perature difference, resistance transducers, DC current and DC voltage
INP 3 and INP 4 (option C): DC current, INP 5: DC current and DC voltage
INP 6: resistance transducer and DC current
2.2 Digital inputs
Opto-coupler for 24 V DC, current sink to IEC 1131 type 1, logic 0 = -3...5 V, logic 1 = 15...30 V, approx. 5 mA
di1 and di2: in all versions,
di3...di7: in option B,
di4...di12: in option C.
2.3 Outputs r section 6.10
Relay contact rating: 500 VA, 250 V,2Aat48...62 Hz
OUT1, OUT2, relay or current or logic dependent of version,
OUT4, OUT5:
OUT 3 (option C): current
2.4 Control outputs
Opto-coupler, grounded load with common positive control voltage, power 18...32 V DC ß 100 mA.
do1...do4: in option B,
do5 and do6: in option C
2.5 Supply voltage
90...260V AC, 48...62 Hz, power consumption approx. 10 VA (equipped with all possible options)
For detailed technical data, see data sheet 9498 737 32133.
2.6 Further "modular" in- and outputs
Further analog and digital inputs and outputs can be provided on the "modular C card"
r see KS98 I/O-extension modules on page 225 ff
2.7 Further external in- and outputs
Further analog and digital inputs and outputs can be connected via CANopen.
r see KS98+ I/O extensions with CANopen page 117 ff
9499 040 50611 Important technical data
9 Analog inputs r sections 3 and 6.9

Table of Contents

Other manuals for PMA KS 98

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the PMA KS 98 and is the answer not in the manual?

PMA KS 98 Specifications

General IconGeneral
BrandPMA
ModelKS 98
CategoryControl Unit
LanguageEnglish