12.7 MONO (monoflop)
The function generates a positive pulse of length Ti
1
at output z1, when a positive flank at trigger input d1 is detected.
It generates a positive pulse of length Ti
2
at output z3, when a negative flank at trigger input d2 is detected.
Pulse duration Ti
1
is adjusted either as parameter Ti1 or read in via inputs Ti1. The origin of pulse duration is selected
via parameter Mode 1. The duration of an output pulse is matched to the new values with changes at inputs Ti1/Ti2.
With input values Ti1/Ti2 ß 0, the pulse is output for the duration of one scanning cycle.
The function is re-triggerable. I.e., if a new trigger condition is detected during a pulse output, the remaining pulse time
to be output is prolonged to a full pulse length. The pulse duration accuracy is dependent of the sampling time, which
is assigned to the function.
Example:
Ti = 0,9s for assignment to
- sampling interval 100ms means that the signal is output during = 0,9s.
- Sampling interval 200ms means that the signal is output during = 1,0s.
- Sampling time 400ms means that the signal is output during = 1,2s.
- Sampling interval 800ms means that the signal is output during = 1,6s.
Inputs/outputs
Digital inputs
d1
Triggerinput: Pulse at z1 and not z1 with positive flank 0 r 1
d2
Triggerinput: Pulse at z3 and not z3 with positive flank 1 r 0
Analog inputs
Ti1
Pulse duration Ti
1
[s] of the pulse generated by d1, when Mode 1 = Para.Ti1.
Ti2
Pulse duration Ti
2
[s] of the pulse generated by d2, when Mode 2 = Para.Ti2.
Digital outputs
z1
Positive pulse of length Ti
1
, when a positive flank at input d1 was detected.
not z1
Negative pulse of length Ti
1
, when a positive flank at input d1 was detected.
z3
Positive pulse of length Ti
2
, when a positve flank at input d2 was detected.
not z3
Negative pulse of length Ti
2
, when a positive flank at input d2 was detected.
9499 040 50611 Logic functions
53 MONO (monoflop)