DESCRIPTION OF PROGRAMMING PARAMETERS
Parameter /
Default Value
7 I SLIP=4.0%(*)
I SLIP COMPENSAT
G19.2.7 / Current
limit factor
Modifies the speed by reducing the output frequency to keep the output current
within a controllable margins (display shows ILT). Adjusting this parameter can
improve the stability of the current limit function taking the motor slip into account.
Note: The following table shows the default values for drives of any nominal
voltage.
Default Values for All Powers
* Adjust mode: When initializing factory settings (1) or manually modifying the
Motor Nominal Power (G2.3) (2). The value of the current limit factor is initialized
according to the table. Values outside the table are estimated according to the
table.
In all cases the adjustment range is + / -30% of initialized value in any of the two
scenarios given (1) and (2).
Note: We recommend this value is adjusted only when the current limit action is
unstable. A low value will improve the stability although the current limit action will
operate earlier.
9 STR FRQ = 0.0%
START FREQUENCY
G19.2.9 / Initial
frequency
Allows setting of an initial frequency that will be applied from the drive at the
moment of starting.
10 DAMPref=OFF
REFER.DAMPING
G19.2.10 /
Damping
reference
In some motors, instable behaviours are generated at low frequencies when the
motors are connected with no load. In that case, set this parameter to 65% as
initial value. If oscillations still are present, reduce the value.
G19.2.11 /
Damping filter
This filter controls the instability. If the value of the parameter 19.2.10 is reduced
down to 45 % and the instability problems are not solved, increase the value of
this parameter.