EasyManuals Logo

Power Electronics SD700 User Manual

Power Electronics SD700
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
SD700FR SERIES
POWER ELECTRONICS
34
DESCRIPTION OF PROGRAMMING PARAMETERS
4.7. Group 7 G7: Start / Stop Mode Configuration
Parameter /
Default Value
Name /
Description
Range
Function
Set on
RUN
1 STOP 1 = RAMP
G7.1 / Stop
mode 1
RAMP
SPIN
It selects the main stop mode of the drive. This value should be configured
appropriately for each application.
OPT
FUNCTION
RAMP
The drive will stop applying a frequency ramp to
stop the motor. The rate of stop is determined in
screen 'G5.2 Decel 1'
SPIN
The drive will turn off the output to the motor. The
motor sill coast to stop. Stopping time is
determined by system inertia.
YES
2 STOP 2 = SPIN
G7.2 / Stop
mode 2
RAMP
SPIN
User can select an alternative stop mode of the drive if required. This value should be
set for each application. For options information see parameter „G7.1 STOP 1=RAMP‟.
Note: Stop mode 1 or 2 can be selected by digital inputs, by comparator output
functions, or by setting a changing speed for stop mode in 'G7.3 BRK STP 2'.
YES
3 BRK STP 2 = OFF
STP2 UNDER SPEED
G7.3 / Changing
speed for stop
mode
OFF=0 to
250%
When this parameter is set to a value other than zero a second stopping profile can be
activated based on motor speed. When the drive receives a stop mode 1 command, it
will stop from steady status to the speed set here. At that moment, the drive will apply
stop mode 2 to complete the stop.
Note: Stop mode 1 or 2 can be selected by digital inputs, by comparator output
functions, or by setting a changing speed for stop mode in 'G7.3 BRK STP 2'.
YES
4 START = RAMP
G7.4 / Start
mode
RAMP
SPIN
SPIN2
It selects the start mode of the drive. This value should be configured
appropriately for each application.
OPT
FUNCTION
RAMP
Drive will start applying a frequency ramp to the motor.
SPIN
In this mode, the motor shaft speed is automatically
searched for and the frequency output of the drive is
set to match the actual motor speed. From this point
the motor is then accelerated normally up to the
reference speed. This allows starting loads that are still
rotating when the drive receives a start command.
Note: This option is valid when the motor is running at
positive rotation direction.
SPIN2
Operates similar than the option „SPIN‟. The difference
lies in the possibility of starting loads that are still
rotating independently of the rotation direction of the
motor.
Note: Start mode 2 (alternative start mode) is selected through a digital input
configured with option ‟22 START MODE 2‟.
YES
5 START 2=RAMP
G7.5 / Start
mode 2
RAMP
SPIN
SPIN2
YES
6 STAR DLY = OFF
DELAY TO START
G7.6 / Start
delay time
OFF=0 to
6500s
Allows setting of a delay time from the moment the drive receives the start command to
the beginning of providing an output frequency to the motor.
Note: After receiving the start command, the drive will wait until the delay time is
elapsed. During this time, the drive status will change to „DLY‟.
YES
7 STOP DLY = OFF
DELAY TO STOP
G7.7 / Stop delay
time
OFF=0 to
6500s
Allows setting of a delay time applied from the moment the drive receives the stop
command until the drive stops providing an output frequency to the motor.
YES
8 STP MIN SP = N
G7.8 / Minimum
stop speed
N
Y
Allows user to stop the motor when the speed is below the SD700FR lower speed
limit.
OPT
FUNCTION
N=NO
In this case, the motor will continue to operate at
minimum speed defined as minimum speed limit
(set in G10.1 or G10.3), even if the speed
reference is below these settings. For example, if
„1 MIN1 SP=+30.00%‟, and the speed reference
is +20.00%, the equipment will operate at
+30.00%, and never below this value.
Y=YES
In this case, the drive will automatically start when
the speed reference is above the value set as
minimum speed limit. While the speed reference
is below this value, equipment will be in 'READY'
status.
If the drive is decelerating and the reference is
below the minimum speed value, then the
equipment will stop by spin.
Note: If you want to stop the motor when the reference is below a fixed speed
setpoint, you should set this parameter to YES. Additionally, you should set the
correct values in 'G10.1 MIN1 SP' or 'G10.3 MIN2 SP'.
YES
9 OFFdly = OFF
DELAY AFTER STOP
G7.9 / Delay time
between stop
and next start
OFF=0.000
to 10.0s
Allows setting a delay time between the moment the drive has stopped and the
next starting. The next time the drive has to start it will consider no additional
delay time unless parameter „G7.6 START DLY‟ had been set to a value different
from OFF.
YES

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Power Electronics SD700 and is the answer not in the manual?

Power Electronics SD700 Specifications

General IconGeneral
BrandPower Electronics
ModelSD700
CategoryInverter
LanguageEnglish

Related product manuals