SD700FR SERIES
POWER ELECTRONICS
74
MODBUS COMMUNICATION
Parameter
Screen
Description
Address
Modbus Range
SV5.1
Local Sp = +100%
Speed reference in local mode.
40124
-20480 to 20480
SV5.2
PID Local = +100%
PID setpoint in local mode.
40149
0 to 32760
SV5.3
Mref 1 = +10.0%
Speed value assigned to Multi-reference 1.
40052
-20480 to 20480
SV5.4
Mref 2 = +20.0%
Speed value assigned to Multi-reference 2.
40053
-20480 to 20480
SV5.5
Mref 3 = +30.0%
Speed value assigned to Multi-reference 3.
40054
-20480 to 20480
SV5.6
Mref 4 = +40.0%
Speed value assigned to Multi-reference 4.
40055
-20480 to 20480
SV5.7
Mref 5 = +50.0%
Speed value assigned to Multi-reference 5.
40056
-20480 to 20480
SV5.8
Mref 6 = +60.0%
Speed value assigned to Multi-reference 6.
40057
-20480 to 20480
SV5.9
Mref 7 = +70.0%
Speed value assigned to Multi-reference 7.
40058
-20480 to 20480
SV5.10
Inch Spd1 = 0.00%
Inch speed 1.
40092
-20480 to 20480
SV5.11
Inch Spd2 = 0.00%
Inch speed 2.
40093
-20480 to 20480
SV5.12
Inch Spd3 = 0.00%
Inch speed 3.
40094
-20480 to 20480
SV5.13
PMP manSP=+0.0%
LOCAL manual speed reference.
42042
-20480 to 20480
SV5.14
PMP MRe1=0.0%
Local setpoint 1 of PID. Multi-reference 1.
42151
0 to 32760
SV5.15
PMP MRe2=0.0%
Local setpoint 2 of PID. Multi-reference 2.
42152
0 to 32760
SV5.16
PMP MRe3=0.0%
Local setpoint 3 of PID. Multi-reference 3.
42153
0 to 32760
SV5.17
PMP MRe4=0.0%
Local setpoint 4 of PID. Multi-reference 4.
42154
0 to 32760
SV5.18
PMP MRe5=0.0%
Local setpoint 5 of PID. Multi-reference 5.
42155
0 to 32760
SV5.19
PMP MRe6=0.0%
Local setpoint 6 of PID. Multi-reference 6.
42156
0 to 32760
SV5.20
PMP MRe7=0.0%
Local setpoint 7 of PID. Multi-reference 7.
42157
0 to 32760
SV5.21
PMP MRe8=0.0%
Local setpoint 8 of PID. Multi-reference 8.
42158
0 to 32760
SV5.22
T AutOFF=OFF
Time for Automatic Stop.
42044
0 to 999
SV5.23
TIME OFF=OFF
It shows the resting time in minutes for the
automatic stopping of the system.
42356
0 to 6000
SV5.24
MAX flow=1000l/s
Level of maximum flow.
42143
0 to 32760
SV5.25
RESET LEVL=+100%
Reset level for the flow control algorithm.
42145
0 to 100
SV5.26
SLEP FLO=0.0l/s
Flow level to sleep the drive.
42324
0 to 32760
SV6.1
TOT= d h
Total time during which the drive is running
(RUN).
40550 Days
40551 Hours
Days Real value = Modbus value
Hours 1 = 0.1 hours
SV6.2
PAR= d h
Partial time during which the drive is running
(RUN).
40552 Days
40553 Hours
Days Real value = Modbus value
Hours 1 = 0.1 hours
SV6.3
CLEAR PARTIAL=N
To reset the counter of partial time for running
status (RUN).
40554
0 to 1
SV6.4
MOTOR ENERGY
Energy consumption in motor operation
41772
0 to 9999kWh/MWh/GWh
SV6.5
REGEN. ENERGY
Energy regenerated in regeneration operation
41774
0 to 9999kWh/MWh/GWh
SV6.6
RSET PRTL ENERG
Reset the partial energy counters
41554
0 to 1
SV7.1
Pow in
Input power
40765
-30000 to 30000
SV7.2
IR
IS
IT
Current per phase
40766
40767
40768
-32000 to 32000
SV7.3
R. Phi Cos
Input phi Cos (DPF)
40770
-100 to 100
SV7.4
Rec T IGBT
Max. IGBT temperature
10048
0 to 150
SV7.5
PLL freq
Internal PLL frequency
40778
-3000 to 3000

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Power Electronics SD700 and is the answer not in the manual?

Power Electronics SD700 Specifications

General IconGeneral
BrandPower Electronics
ModelSD700
CategoryInverter
LanguageEnglish

Related product manuals