C6
Rev.304
A. See page 2 for further model number information.
B. The flame sensor shown - UV (Ultra Violet) or CC (Cad Cell). Other flame
sensors such as Lead Sulfide and photo cell are available to comply with
specifications or codes.
C. If separate pump is supplied, HP may be reduced. For positive pressure
applications on C1 burners with integral pump firing over 8 GPH or some OEM
boilers, a 1/2 HP motor and oversized fan are required on oil and gas/oil burners.
D. Capacities listed are based on 0.20" W.C. positive pressure. Derate capacities
approximately 5% for each +.50" W.C. combustion chamber pressure,
except for C5-OB and C5-G(O)-30B, which are rated for 250 BHP at +1.2"
W.C. All capacities based on 2000' elevation. Derate capacity by 4% for each
additional 1000' elevation.
E. At inlet to main shutoff cock with burner operating at maximum input rate.
If auxiliary gas valves are used, C2-G(O)-20A through C4-G(O)-30 inlet
pressure of 28" (1#) are permitted when using optional 325-3 pilot regulator.
F. Model numbers will always reflect the standard U.L. listed gas train sizes
to correlate with U.L. input listings. The actual train size may vary, depending
on local gas supply pressures available.
G. and H. Suction line and oil filter must be sized to provide these suction capacities.
Do not size suction lines or filter capacities based on burner firing rates.
See page 11 for further information.
I. C2-OB will be supplied with a UV sensor if firing rate is above 20 GPH
(unless specified otherwise).
Model CO (Oil)
C1-O(S) CC
1
/
3
9.7 - 32.3 - - 19(J)
1
/
3
19(J)
C2-OA(S) CC
3
/
4
15.7 - 52.3 - - 70(K)
1
/
3
70(K)
C2-OB(S) CC(I) 1
1
/
2
22 - 73.5 - - 40
1
/
3
40
C3-O UV 2 33.7 - 112.0 - - 105
1
/
2
105
C3-OB UV 3 37.5 - 125.0 - - 135
3
/
4
135
C4-OA UV 5 45 - 150.0 - - 135
3
/
4
135
C4-OB UV 5 56 - 190.0 - - N/A
3
/
4
135
C5-O UV 7
1
/
2
75 - 250.0 - - N/A 1 250
C5-OB UV 7
1
/
2
75 - 250.0 - - N/A 1 250
C6-O UV 10 101.5 - 340.0 - - N/A 1 250
C7-O UV 15 121.4 - 404.0 - - N/A 1 265
C7-OB UV 20 126.4 - 421.0 - - N/A 1 265
C8-O UV 15 136.4 - 454.0 - - N/A 1 265
Model CG (Gas)
C1-G-10 UV
1
/
3
- 980 23.5 5.6-14 1" ---
C1-G-12 UV
1
/
3
- 1360 32.3 5.3-14 1
1
/
4
" ---
C2-G-15 UV
1
/
2
- 2200 52.3 5.2-14 1
1
/
2
" ---
C2-G-20A UV
3
/
4
- 2500 60.0 4.8-14 2" ---
C2-G-20B UV 1 - 3080 73.5 4.8-14 2" ---
C3-G-20 UV 1
1
/
2
- 4200 100.0 5.9-14 2" ---
C3-G-25 UV 1
1
/
2
- 4718 112.0 7.0-14 2
1
/
2
" ---
C3-G-25B UV 3 - 5250 125.0 7.2-14 2
1
/
2
" ---
C4-G-25 UV 3 - 6300 150.0 8.0-14 2
1
/
2
" ---
C4-G-30 UV 5 - 7840 190.0 12.1-14 3" ---
C5-G-30 UV 7
1
/
2
- 10500 250.0 19.9-28 3" ---
C5-G-30B UV 7
1
/
2
- 10500 250.0 17.8-28 3" ---
C6-G-30 UV 10 - 14215 340.0 26.5-28 3" ---
C7-G-30 UV 15 - 17,000 404.0 40-280 3" ---
C7-G-30B UV 20 - 17,700 421.0 40-280 3" ---
C8-G-30 UV 15 - 19,100 454.0 50-280 3" ---
Table 2
Standard Burner Ratings and Component Data Power Flame Certified Capacity 0.2” W.C. Positive Pressure (D)
Burner Standard 3450RPM GPH MBTU/HR. Nominal Gas Standard
Model Flame Blower Maximum Natural Gas Boiler Pressure Gas Train
(A) Sensor (B) Motor Maximum H.P. Required Size (F)
H.P.(C) Inches
W.C. (E)
Min.Max.
Burner
Mounted
Oil Pressure
Pump Suction
Capacity In
GPH(G)
Separate Driven
Oil Pressure Pump
If Supplied (H)
Motor
H.P.
Suction
Capacity
In GPH
Burner Pump Suction Capacity
Model CGO (Combination Gas/Oil)
C1-GO-10 UV
1
/
3
7 980 23.5 5.6-14 1" 19(J)
1
/
3
19(J)
C1-GO-12 UV
1
/
3
9.7 1360 32.3 5.3-14 1
1
/
4
" 19(J)
1
/
3
19(J)
C2-GO-15 UV
3
/
4
15.7 2200 52.3 5.2-14 1
1
/
2
" 70(K)
1
/
3
70(K)
C2-GO-20A UV 1 17.5 2500 60.0 4.8-14 2" 40
1
/
3
40
C2-GO-20B UV 1
1
/
2
22 3080 73.5 4.8-14 2" 40
1
/
3
40
C3-GO-20 UV 2 30 4200 87.0 5.9-14 2" 105
1
/
2
105
C3-GO-25 UV 2 33.7 4718 112.0 7.0-14 2
1
/
2
" 105
1
/
2
105
C3-GO-25B UV 3 37.5 5250 125.0 7.2-14 2
1
/
2
" 135
3
/
4
135
C4-GO-25 UV 5 45 6300 150.0 8.0-14 2
1
/
2
" 135
3
/
4
135
C4-GO-30 UV 5 56 7840 190.0 12.1-14 3" N/A
3
/
4
135
C5-GO-30 UV 7
1
/
2
75 10500 250.0 19.9-28 3" N/A 1 250
C5-GO-30B UV 7
1
/
2
75 10500 250.0 17.8-28 3" N/A 1 250
C6-GO-30 UV 10 101.5 14215 340.0 26.5-28 3" N/A 1 250
C7-GO-30 UV 15 121.4 17,000 404.0 40-280 3" N/A 1 265
C7-GO-30B UV 20 126.4 17,700 421.0 40-280 3" N/A 1 265
C8-GO-30 UV 15 136.4 19,100 454.0 50-280 3" N/A 1 265