Specifications
49
Powerware
®
5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
Table 6. Battery
Configuration (10) 12V, 5 Ah internal batteries
EBM Configuration PW5125 120 EBM: 120V, 30A
Type Sealed, maintenance-free, valve-regulated, lead-acid
Charging Internal battery: less than 3 hours to 90% usable capacity at nominal line voltage after full load
discharge
External battery: recharging at 80% load or less is recommended; no more than 16x discharge
time to 90% usable capacity at nominal line voltage after full load discharge; an external charger
is recommended for faster recharge times when using more than 2 EBMs.
Monitoring Advanced monitoring for earlier failure detection and warning; auto detection of additional EBMs
(if using LanSafe III Power Management Software, the EBM configurator must be used for
accurate reporting of EBM battery times).
Table 7. Battery Run Times (in Minutes at Full/Half Load)
Model Internal UPS Batteries 1EBM 2EBMs 3EBMs 4EBMs
2400 VA 7/19 35/73 60/124 85/177 110/229
3000 VA 5/15 25/61 49/103 69/146 90/190
NOTE
Battery times are approximate and vary depending on the load configuration and battery charge.