3332
MENU MAP ON SCREEN BRIEF DESCRIPTION RANGE DEFAULT SETTING
High Pressure ESDs HPR ESDs Number of High Pressure Shutdowns. 0 to 1000 N/A
Low Pressure ESDs LPR ESDs Number of Low Pressure Shutdowns. 0 to 1000 N/A
Level ESDs LVL ESDs Number of Level Contact Shutdowns. 0 to 1000 N/A
Thermocouple Errors TC Errs Number of Thermocouple Shutdowns. 0 to 1000 N/A
Terminal Card Errors Term Errs Number of Terminal Card Shutdowns. 0 to 1000 N/A
System Errors Sys Errs Number of System Errors Shutdowns. 0 to 1000 N/A
View Event Log View Event Log? Log of recent events Yes/No No
Clear History Clear History? Clears all History and logged events Yes/No No
SYSTEM INFO (MENU 3)
This menu contains diagnostic information about the system.
MENU MAP ON SCREEN BRIEF DESCRIPTION RANGE DEFAULT SETTING
High Temp TC Reading Hi Temp TC Current High Temp Thermocouple
reading
-50˚C to
1350˚C
N/A
Process Temp TC Reading Proc TC Current Process Thermocouple reading -50˚C to
1350˚C
N/A
4-20mA Output Percent 4-20
Output
Current status of the 4-20mA Output 0 to 100% N/A
Ambient Temp Ambient Temp Current ambient temperature. Used
for thermocouple cold junction
compensation.
-55˚C to 65˚C
-70˚F to 150˚F
N/A
Voltage Reading System Voltage Current voltage applied to the system 8V to 35V N/A
Commision Date Commission
Date
Date that the system was commissioned
(if entered by user)
DD-MMM-
YYYY
N/A
Location Location The install location of the system (if
entered by user)
N/A N/A
Control State Control State Debug Information N/A Hidden
Terminal Card State Term Card Debug Information N/A Hidden
SYSTEM SETUP (MENU 4)
This menu contains various optional system settings. It cannot be accessed while the PF2100 is running.
MENU MAP ON SCREEN BRIEF DESCRIPTION RANGE DEFAULT SETTING
Auto Restart Auto
Restart
Enables system to restart from a power
failure or high voltage event.
On/Off Off
Purge Time Purge Time Adjusts the time from all valves closed
to Pilot relight attempts
10 - 900 sec 30 sec
Pilot to Main Delay Pilot to Main
Delay
Adjusts the time from Pilot proven to
Main Valve opening
5 - 600 sec 15 sec
Restart Attempts Restart
Attempts
Adjusts the number of Restart Attempts
after an unexpected flame failure before
a shutdown
0 - 3 3
Level Event Restart Level Event
Restart
Enables recovery from a Low Level
event
On/Off Off
Pressure/Level Delay PRS/LVL
Delay
Pressure and Level shutdown delay On/Off Off
MENU MAP ON SCREEN BRIEF DESCRIPTION RANGE DEFAULT SETTING
Pressure Restart
PRS Restart
Allows the system to automatically
restart when a low pressure event
clears. Can also enable control of the
main valve based on the Low Pressure
Contact or Low Pressure Setpoint.
Enabled,
Disabled,
Main Control
Disabled
Alarm Mode Alarm Mode Adjusts the behaviour of Status Contact
relative to Start Contact
Alarm when
Off,
No Alarm
When Off
No Alarm when
Off
Password Enable Password Enable Password Protection (Menu 1-3) On/Off Off
Display Sleep Display Sleep Enable Sleep Mode for the Display Never, After
10 Min
Never
Pilot Valve Power Setting Pilot Solenoid
PWM
Adjusts the Pilot Valve PWM duty cycle Off, 80%,
60%, 40%,
20%
60%
Main Valve Power Setting Main Solenoid
PWM
Adjusts the Main Valve PWM duty cycle Off, 80%,
60%, 40%,
20%
60%
System Voltage Setting System
Voltage
Configures the expected input voltage
for the system
12V, 24V 12V
Temperature Display Units Temp Units Configures the temperature units
displayed by the system
Fahrenheit,
Celsius
Celsius
Commission Date Entry Commission
Date
Set the date that the system was
commissioned
DD-MMM-
YYYY
01-JUN-2012
Commission Location Entry Commission Loc Set the install location of the system. 14
Characters Max.
A-Z, 0-9, -./
Reset to Factory Defaults Rest to Factory
Defaults?
Restore all settings to the factory default Yes/No No
CONTROL SETUP (MENU 5)
This menu contains various optional Process Control settings. It cannot be accessed while the PF2100 is
running.
MENU MAP ON SCREEN BRIEF DESCRIPTION RANGE DEFAULT SETTING
High Temp ESD Setpoint High Temp
ESD SETPNT
Adjusts the High Temperature shutdown
setpoint
2 to 1350˚C
36 to 2462˚F
90˚C
194˚F
Process Control Input Process Control Configure the thermocouple used as the
Process Temperature
Process TC,
AUX TC
Process TC
Low Fire Enable Low Fire Enables Low Fire feature and setpoint Disabled,
on at Proc
Setpnt, on
at Low Fire
Setpnt
Disabled
Low to High Fire Delay Low to High Fire
Delay
Adjusts the time from Low Fire Valve
opening to High Fire Valve opening,
when Low Fire is enabled. Values set
above 255 seconds are automatically
set to the value minus 255 seconds. For
example, inputting 275 seconds sets the
actual delay to 20 seconds.
30 - 300 sec Hidden, 30 sec
Pilot Off Enable Pilot Off Enables Pilot Off feature and setpoint Disabled,
Enabled
Enabled
Aux Temp Mode AUX Temp Mode Configures how the Auxiliary
Thermocouple is used.
Disabled,
Display Only,
Temp Main
Ctl, Temp ESD
Disabled