EasyManua.ls Logo

Prolon VC2000 Series - System Start-up

Default Icon
98 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Before powering up any Prolon control system for the rst time, a safety check list should be performed on all devices,
their wiring, and connections. This will ensure a successful start-up. (Consult: Installation Checklist PL-INSTL-
CHECKLIST-EN document for complete details).
Although not exhaustive, that list should include:
• Checking the power supply source
Shielding and grounding of appropriate cables
Addressing the controllers
Setting up Termination / Bias resistors where needed
• Powering up and checking indicator light behavior
Power Supply Source
Supply to controllers must be 24VAC +/- 10%. The transformers used must have their common tab grounded to earth. All
controllers must share same the same 24vac Live -vs- Neutral terminal connections, as incorrect supply voltage polarity may
not cause damage but will cause communication failure until corrected.
Addressing Controllers
All controllers must have a valid address (anywhere from #1 to #127) to be able to communicate on a network. Even if left
standalone, zone controllers (C1050, VC2000) must still have an address to communicate with their own digital wall sensor.
•C1050 & M2000 controllers use dipswitches to set their address. They have no default addresses
•NC2000 Network Controller uses virtual addressing. It has factory set default address: #99
•T1100 Thermostat uses virtual addressing. It has factory set default address: #101
•VC2000 VAV controller uses virtual addressing. It has no default address
Terminating & Bias Resistors
Each communication segment of a networked system must have Terminating (end-of-line) as well as BIAS resistors enabled.
Checkthattheterminatingresistorjumpersareenabledonlyoneachofthetwooppositecontrollersonthecommunication
segment.Also,asinglecontrollermusthaveitsBIASresistorjumpersenabledaswell(Consultsection#4fordetails).
Grounding of Cables
Communicationbusshieldonanysegment(INT&NET)mustbegroundedatonlyoneendofthesegment,joinedbetweenall
networked controllers, and left isolated at the other end. (Consult PL-INSTL-WIRING-EN for complete details).
System Start-up
Shielded sensor wire, when
used, must only be grounded
at one extremity, typically at
the Master controller end.
5-5

Related product manuals