EasyManua.ls Logo

Prolon VC2000 Series - Page 76

Default Icon
98 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
• Eg:pressureread:0.20”,adjustsetpointto(pressureread+20%)=0.24,0.05”=dierential.
Return to the “Zone Damper Overrride” and enter 25%, click “Apply”.
Check the bypass damper opening on the home page as well as physically according to the increase in pressure. Inverse
the opening direction of the bypass damper if need be.
Return to the home page, click “Network” and then “Other. Remove the “Zone Damper Override, press “Apply”.
Cooling and heating operations
From the home page of the unit controller, point and right-click each item to be checked to activate the override mode. You
can check the economizer’s damper(s) (if applicable), the cooling stage(s), the heating stage(s) and/or the modulating
heating output from the unit. Physically check the proper functioning of each of these elements.
Return to the “Edit Display” menu and remove the absolute overrides and click “Apply”.
8-5

Related product manuals