3 Set the Module Properties values as follows:
Parameter
Value
Name
Enter a module identification string. Example: GSC
Description
Enter a description for the module. Example: Enhanced
Generic ASCII Serial Communication Module.
Comm Format
Select DATA-SINT.
Slot
Enter the slot number in the rack where the MVI56E-GSC
module is located.
Input Assembly Instance
1
Input Size
500
Output Assembly Instance
2
Output Size
496
Configuration Assembly Instance
4
Configuration Size
0
4 On the Connection tab, set the RPI value for your project. Click OK to
confirm.