MVI56E-GSC/GSCXT CompactLogix or MicroLogix Platform MVI56E-GSC Configuration
Enhanced Generic ASCII Serial Communication Module User Manual
ProSoft Technology, Inc. Page 53 of 140
April 24, 2017
For each termination type, you must also enter values in the following parameter
configuration tags. Streaming mode is not recommended for general use, as it
creates heavy demands on the ControlLogix processor and requires time-critical
programming logic to properly process.
For Termination Type
Receive Parameters to Set
Terminating Characters
GSC.PortX.RTermCnt
GSC.PortX.RTermChar
Message Timeout
GSC.PortX.RTimeout
Intercharacter Delay
GSC.PortX.RDelay
Packet (String) Length
GSC.PortX.RPacketLen
2.2.3 Port[x].Baudrate
This is the baud rate to use on the port. Enter the baud rate (bits per second) as
a value. All devices on this port must communicate at the same baud rate. For
example, to select 19K baud, enter 19200.
The following table describes the valid parameters for this configuration entry.
Value
Baud Rate (bits per second)
110
110 Baud
150
150 Baud
300
300 Baud
600
600 Baud
1200
1200 Baud
2400
2400 Baud
4800
4800 Baud
9600
9600 Baud
19200
19200 Baud
384
38400 Baud
576
57600 Baud
115
115200 Baud
2.2.4 Port[x].Parity
Parity is a simple error checking algorithm used in serial communication. This
parameter specifies the type of parity checking to use. All devices connected to
the port must use the same parity.
Value
Description
0
None
1
Odd
2
Even
3
Mark
4
Space.