15.0 3200 Features Specification
Non-latching Zones 1 or both zones may be programmed as non-latching. Panel resets when cause of the
fire is cleared. Global fire contacts do not activate.
Zone Disablements 1 or both zones can be disabled to prevent faults and activation.
Alarm Disablements Alarm Circuits can be disabled to prevent faults and activation.
Coincidence on Zones Programmable (both zones must activate together to trigger panel). A default 2-minute
time-out is given if any one coincidence zone activates.
A manual activation on a coincidence zone will also activate the panel.
Note: The 3200 is no longer compliant to EN54 if zone coincidence is
programmed.
Zonal Test 1 or both zones. When triggered operates alarm outputs for 4 seconds, then resets
panel (assuming no other non-test zone are activated).
End of line type Programmable. Can be programmed as either resistive (8.2kΩ) or capacitive (100µF +
22Ω).
Ability to Distinguish between When the Manual Call Point Incorporates a 180Ω resistor.
Manual or Automatic Zone Activation
Ability to re-activate a silenced zone A zone activated by an automatic detector, then silenced, is re-triggered by
by a manual Call Point Activation a Manual Call Point Activation.
Note: Due to a policy of continuous improvement, Protec Fire Detection PLC reserves the right to alter the specification without
prior notice.