Publication ERSC-1521 Rev 1.0 – February 2019
Connecting to Rockwell PLCs
Step 4
In the Module Definition
window you will see the
default settings from the
EDS file. The EDS file only
allows SINT data type to be
default. This needs to be
changed to INT.
See Note ① below.
Note: Your Revision information
shown may show a newer value
than shown in this example based
upon the EDS file you downloaded
from the web site.
Click the right of the Size box
to show a drop down box
and then select INT
Once you have selected INT
as the data size, you will
notice the input and output
sizes now reflect the register
quantities as described in
the ConveyLinx-Ai2 PLC
Developer’s Guide for ZPA
mode. Click OK.
Step 5
When you click OK, a
warning will appear to tell
you that you are changing
the default parameters.
Click Yes.
Always change
SINT to INT!