15
LED Indicators Instructions
Battery
Status
Protection
/ Alarm /
Normal
STATUS
(green)
STATUS
(red)
Capacity SOC
Descriptions
Shut Down
Off
Off
Off
Off
Off
Off
All off
Sleep
Normal
Flash2
Off
Off
Off
Off
Off
Indicates Sleep Mode,
to save the power.
Idle
Normal
Light
Off
Off
Off
Off
Off
Indicates save power
mode.
Alarm
Light
Off
Off
Off
Off
Off
Indicates the battery
voltage or
temperature is high or
low.
Protection
Off
Light
Off
Off
Off
Off
Indicates the battery
voltage or
temperature is over or
under.
Charge
Normal
Light
Off
The highest capacity
indicator LED flashes (flash
2), others lighting
The highest capacity
indicator LED flashes
(flash 2), others lighting,
horse race lamp when
SOC= DODH;
Alarm
Light
Off
Protection
Off
Light
Off
Off
Off
Off
Stop charging,
STATUS(red) lighting
Discharge
Normal
Flash2
Off
Indicate based on
capacity
Indicate based on
capacity
Alarm
Flash2
Off
Protection
Off
Light
Off
Off
Off
Off
Stop discharging,
STATUS(red) lighting
Abnormal
Power On
Fault
Off
flash 4
Off
Off
Off
Off
Stop
charging/discharging,
STATUS(red) lighting
Other Fault
Off
light
Off
Off
Off
Off
STL Fault
Off
flash 2
flash 2
MCU self-check
problem
Note: The flashing instructions, flash 1 - 0.25s light / 3.75s off; flash 2 - 0.5s light / 0.5s off; flash 3 -
0.5s light / 1.5s off; flash 4 - 1s light / 1s off.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pylontech PowerCube-M1-C and is the answer not in the manual?

Pylontech PowerCube-M1-C Specifications

General IconGeneral
BrandPylontech
ModelPowerCube-M1-C
CategoryStorage
LanguageEnglish

Related product manuals