EURO 46, 162 & 280 Programming Manual
Page: 46
Timer Function Range
the wireless ZEM within that period will cause a supervision fault. This
must be programmed to 2 hours or less for compliance to EN50131.
Wireless
Jamming Time
This option is only applicable if wireless devices are installed. It is the time
window that if a wireless device had its signal ‘blocked’ a fault would
display. For example, if the time is set to 30 seconds, then if a wireless
device is ‘jammed’ longer than 30 seconds a fault will be displayed. This
must be programmed to 30 seconds or less (but not zero) for compliance
to EN50131.
0-100 seconds
Service Time This is a timer that can be set in days, and will display a message to the
user warning that a service is due. An Engineer code will clear the
message.
367 days