D9000/D7000 Series Operation & Installation Manual
Page 62
74-07692-000-C 4/97
Standby Battery Requirements
Household Burglary and Commercial
Burglary
Four hours of standby battery capacity required.
Bank Safe and Vault
72 hours of standby battery capacity required (UL
365). Aux Power current for all devices, including
control centers, must be limited to 300 mA or less
to meet this requirement.
Central Station or Local Fire Alarm
24 hours of standby plus 5 minutes of alarm
operation required. See
Central Station or Local
Systems Ampere-Hour Calculation Formula
in the
Standby Battery Calculation for NFPA 72 Fire Alarm
Applications
section.
Remote Station or Auxiliary Fire Alarm
60 hours of standby plus 5 minutes of alarm
operation required. See
Remote Station or Auxiliary
System Ampere-Hour Calculation Formula
in the
Standby Battery Calculation for NFPA 72 Fire Alarm
Applications
section.
Household Fire Warning Equipment
24 hours of standby plus 4 minutes of alarm
operation required. See
Household Fire Ampere-
Hour Calculation Formula
in the
Standby Battery
Calculation for NFPA 72 Fire Alarm Applications
section.
www.PDF-Zoo.com
firealarmresources.com

Table of Contents

Other manuals for Radionics D7412

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Radionics D7412 and is the answer not in the manual?

Radionics D7412 Specifications

General IconGeneral
BrandRadionics
ModelD7412
CategoryControl Systems
LanguageEnglish

Related product manuals