EasyManua.ls Logo

RC GROUP TRIPACK Series - Table of General Maintenance Jobs

Default Icon
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 7 - MAINTENANCE INFORMATION
RC GROUP S.p.A I_TRP_0909_GB
43
7.3 TABLE OF GENERAL MAINTENANCE JOBS
INTERVAL
JOBS TO BE EFFECTED Every day
Begin of
season.
Every 500h
or 2 months
Begin of
season.
Every 1000h
or 3 months
Expert Operator
Checking of any alarms (see § 6.7)
z
External visual checking for any leak
z
Checking of the water temperature at the outlet
(see § 6.3)
z
Checking of the hydraulic circuits’ filters
(see diagrams § 4.6 and 4.7)
z (1)
Checking of pressure vessels (see § 7.5)
z
Specialized Engineer
Checking of the water flow and cleaning of
exchangers (see § 7.6)
z
Checking for any leak in the refrigerating circuit
z
Checking of contactors
z
Checking of the electrical connections’ tightening
z
Checking of the noise produced by fans’ bearings
z
Checking of the refrigerating circuits’ working parameters.
In every circuit check:
- the
condensation pressure, comparing it with the
data of the heat source used (water temperature)
- the evaporation pressure, comparing it with the
data of the heat source (water temperature)
z
- the suction temperature
- the manometric suction temperature
- the discharge temperature
- the manometric discharge temperature
-
the liquid temperature
z
- overheating
-
undercooling
z
- the line voltage on the three phases
- the ground insulation
- the absorbed current (100% and in partial load
operation)
z
- the hours of operation
-
the number of start-ups
z
(1) Every 50 hours during the first month of operation.

Table of Contents