EasyManuals Logo

RC GROUP TRIPACK Series User Manual

Default Icon
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #45 background imageLoading...
Page #45 background image
Chapter 8 - TROUBLESHOOTING
RC GROUP S.p.A I_TRP_0909_GB
45
8 TROUBLESHOOTING
Alarm
Description
Function
Cause
Remedy
R
estart
AL01
Wrong phases
sequence
Compressor
rotation sense
Electric Re-connect 2 phases
A
AL05
Low pressure for
refrigerant circuit
Hydraulic
circuit
Insufficient water flow
Check the hydraulic circuit
A/M
Refrigerant
circuit
Low refrigerant
charge
Contact an After-Sales
Service authorized by the
manufacturer
Faulty working
AL11
High pressure for
refrigerant circuit
(pressure switch)
Refrigerant
circuit
High outdoor
temperature
Contact an After-Sales
Service authorized by the
manufacturer
M
Chilled water set-
point too high
Dirty condenser
AL14
High pressure for
refrigerant circuit
(pressure transducer)
Refrigerant
circuit
High outdoor
temperature
Contact an After-Sales
Service authorized by the
manufacturer
A/M
Chilled water set-
point too high
Dirty condenser
AL20
Irregular working
temperature and
pressure in the
refrigerant circuit
Refrigerant
circuit
Faulty working
Contact an After-Sales
Service authorized by the
manufacturer
M
AL23
AL24
Thermal protection
of the compressor
1-2
Compressor
Unbalanced power
supply
Check the line voltage
M
Blackout
Compressor failure
Contact an After-Sales
Service authorized by the
manufacturer

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RC GROUP TRIPACK Series and is the answer not in the manual?

RC GROUP TRIPACK Series Specifications

General IconGeneral
BrandRC GROUP
ModelTRIPACK Series
CategoryChiller
LanguageEnglish