2 -
LM800/ 8000
COMMON CALIBRATION
6
“Sample type” : “STD” sets the system to sample a dynamic weigh procedure in the standard format, as used
in the Loadmaster 8000 series with earlier S/W version PS300-026 rev.38
“ADV” sets the system to sample a dynamic weigh procedure in a new format. This mode should generally be
selected, as it should be consistently more accurate in use.
Where this option is selected it will be necessary to mount the Ref / Dir sensors about 200mm from the boom
pivot pin, centre,set.
2.1.1 General setup for loading shovels
Check that the initial settings are as given below. These are suitable for
almost all makes and model of machine whether operated in Dynamic
weighing mode or in Static weighing mode.
Setting Dynamic or Static mode
Num. Samples 1
Sample Time 1.2
Auto Static 2.0
Ram Ratio 1.3000
Live Static On
Static Speed Off (‘On’ for CAT 966, 972 and 980)
Dual Sensor Diff
Nudge On
Zero Check Off
Mode Dyn/Stat
Angle Sensor Off
Sample type ‘ADV’ (in accordance with Ref. /Dir. Sensor installation)